Search...

⌘K

POINT BL-P01

Field connection device for sensors (reed switches, duress buttons, PIR, temp/light sensors). Long-range 2+ km line-of-sight direct comms with BASE or BASE MINI. Up to 2-year lithium battery life.

Short Description

POINT is a compact wireless input module designed to securely transmit alarm and monitoring signals across large-scale sites without cabling. Powered by an internal battery, POINT enables rapid deployment of external detectors and sensors, supporting reliable two-way supervised communication through the B-LINK network.

Main Applications

  • Wireless alarm input expansion

  • Door position monitoring

  • Plant & safety detector integration

  • Perimeter detection

  • Temporary site monitoring

Inputs

1 x Supervised Input
Configurable for external detectors or switches

Specifications

Category

Detail

Communication

B-LINK encrypted long-range (two-way)

Frequency

433 MHz & 2.4 GHz

Wireless range

>2 km line-of-sight*

Input channels

1 supervised

Power supply

3.3 V battery

Battery life

Typical 2 years (depending on heartbeat)

Status LEDs

Green TX / Blue Setup

Configuration

Web GUI

Ambient temperature

0 °C to +60 °C

Supervision

Adjustable heartbeat (1–180 min)

Dimensions (mm)

51 × 71.5 × 22

Weight

100 g

Mounting

Indoor, conduit mount optional

Set-Up Guide

Remove then reinsert battery

  1. Hold tamper button until blue LED flashes

  2. Connect to Wi-Fi:
    B-LINK POINT-(last 6 MAC)
    Password: wireless

  3. Go to 192.168.1.1

  4. Set Point ID, Site ID, Receiver ID

  5. Configure heartbeat interval

  6. Enable tamper mode if required

  7. Press Save → Wait for green LED

  8. Press Restart to apply settings

For advanced features, refer to the downloadable Quick Setup Manual.

Remove then reinsert battery

  1. Hold tamper button until blue LED flashes

  2. Connect to Wi-Fi:
    B-LINK POINT-(last 6 MAC)
    Password: wireless

  3. Go to 192.168.1.1

  4. Set Point ID, Site ID, Receiver ID

  5. Configure heartbeat interval

  6. Enable tamper mode if required

  7. Press Save → Wait for green LED

  8. Press Restart to apply settings

For advanced features, refer to the downloadable Quick Setup Manual.

Troubleshooting

Issue

Action

Device not enrolling

Confirm Site ID + Receiver ID match BASE

Short battery lifespan

Increase heartbeat interval

No input reaction

Check NO/NC setting and wiring

Signal interruptions

Avoid mounting on or behind metal

Tamper alarm

Verify mounting and tamper button seating